High-Voltage Fuse for Overload Protection of Oil-Immersed Transformer

  • Model NO.: PRNT-15.5/-1.8
  • Type: Current Fuse
  • Shape: Insert
  • Fusing Device: Link Break
  • Trademark: zhenli
  • Origin: Xi′an
  • Breaking Capacity: High
  • Usage: High Voltage
  • Fusing Speed: FF
  • Standard: UL
  • Transport Package: Carbon
  • HS Code: 8535100000

High-voltage fuse for overload protection of oil-immersed transformer

This product applies to indoor AC 50~60Hz system with the rated voltage of 15.5kV and shall be used in series with the backup fuse for oil-immersed transformer overload protection, and can provide the full range protection for indoor power system. The product has passed the type test conducted by the national high-voltage electrical equipment quality supervision and inspection center, and conforms to GB15166.2 and IEC282-2.
Model:
 High-Voltage Fuse for Overload Protection of Oil-Immersed Transformer

Basic parameters:
 
Product Model Rated Voltage
 (kV)
Maximum Voltage
 (kV)
Rated Current
 (A)
Rated Maximum Breaking Current (kA) Application Conditions
PRNT-15.5 15.5 17.2 6,10,16,25,40,50,
60,100,140
1.8 Transformer oil
Outline and installing dimensions:
 High-Voltage Fuse for Overload Protection of Oil-Immersed TransformerHigh-Voltage Fuse for Overload Protection of Oil-Immersed Transformer


                                           Fig.2 Dimensions of the Overall and Installation
Main technical performance:
 High-Voltage Fuse for Overload Protection of Oil-Immersed Transformer          
Fig.3 the fuse and backup fuse protection feature
Note: Point A: the intersection of two curves
Point B: rated minimum breaking current of backup fuse
Point C: rated maximum breaking current of fuse
During the operation, point A must be present and point B is above point A
Point C is below point A.
 High-Voltage Fuse for Overload Protection of Oil-Immersed Transformer

  Fig. 4 Time - current characteristic curve
 
 
 
 
Installation and use
1. When mounting the fuse into the tank, ensure the oil level is within the range as shown in Fig. 2
2. When replacing the fuse, open the buckle on the handle and turn the handle for 90° to eliminate the adhesion between the sealing gasket and outer tube. Remove and replace the handle.
3. For the installation of three-phase fuse, replace all three phases unless you can confirm that the fault current passes through one phase.
 